each Carriage Return (CR) it receives. You should also tell it NOT to scroll automatically
after the eightieth column is filled. If either of these are on, the screen will be displayed
'double spaced'. This won't cause any problem, but will make it hard to see the whole
screen at one time.
If you have hooked up the Br-ANA to your computer and it still doesn't seem to re-
spond to the keyboard, the first thing to check is that you are attached to the right serial
port. The easiest way to do this is to disconnect the Br-ANA and short between the Tx
data out and Rx data in pins on your USB-to-Serial converter. For a RS-422 port, this
means temporarily shorting the Rx+ to the Tx+, and Rx- to the Tx-, so two jumpers will
be needed. On the USB-Rs232/422, the pinout is as follows:
POSITION
WIRE #
COLOR
SIGNAL NAME:
LEFT
RIGHT
1
white
Signal Ground
2
black
Rx- data in to Converter
3
red
Rx+ data in to Converter
4
green
Tx- data out of Converter
5
yellow
Tx+ data out of Converter
6
blue
Ground
While still running the modem program, anything you type should be shown on the
screen while these jumpers are in place, while nothing will appear when you remove
them. If your computer passes this test, then you are using the right serial port and the
problem is most likely the baud rate setting or in your wiring to the Br-ANA. If you get
characters on the screen even with the jumpers removed from the serial port, it means
you probably need to set the 'echo' mode to 'none' or 'full duplex' and try this test again.
To enter the configuration mode you need to press the ʻconfigureʼ button on Gil-
derTerm, or type the following if you are not using GilderTerm. The (address) is replaced
by the HEX value set on the ADDRESS switches on the front of the Br-ANA:
m5AA5(address)
If any other card is in configuration mode (or even if it just thinks another card is in
configuration), the Br-ANA won't be able to enter configuration mode. To exit any other
card from configuration type 'XN'. You can then try entering configuration again.
For eight bit resolution outputs, the menu will appear as follows. Decimal values have
been selected for the numbers. At the top of the screen the size of the Animation Data
Gilderfluke & Co.• 205 South Flower Street • Burbank, California 91502 • 818/840-9484 • 800/776-5972 • fax 818/840-9485
Br-ANA Manual / December 18, 2012 10:21 AM / page 32 of 60