E-Stop and Load Unload shows. This is because although
you want these inputs to trigger an error while the motion
base is in motion, you donʼt want this to trigger an E-Stop
when the doors are opened for the passengers to be loaded
and unloaded.
c) Electric Motion Bases and other Installations that donʼt use
the Kp-300 Blocking Valve Output: If you donʼt want to allow
shows to be run if there is an E-Stop condition present, you
can configure one of the two bypass busses to momentarily
(for just one frame) bypass all the possible error inputs at the
very start of all shows
17
. At the end of the bypass buss pulse,
any error conditions that remain will trigger the E-Stop to keep
even the video and audio from running. This technique should
be used in applications that donʼt use the Blocking Valve Out-
put. Typical of these are most electric motion base installa-
tions.
If you are using the Seat Belt Logging features of the Kp-300, be
sure you donʼt configure the Kp-300 to bypass any inputs that are to
be logged during the time during which they need to be logged. By-
passing an input will convince the Kp-300 that the inputs are in the
ʻsafeʼ position, and so they will not be logged as ʻunoccupiedʼ.
The Show Pause functions are usually disabled during the E-Stop
and Load/Unload shows by the Show Pause Reset Input from the
Smart Brick System. Inputs that trigger a Show Pause are usually not
needed during the E-Stop and Load/Unload shows anyway, so there is
no need to bypass them separately during these shows.
3) E-Stop Show Running input to Kp-300
This input is used by the motion control profile to indicate that an E-Stop Show
is running. The E-Stop Show Running output is normally only programmed active
during the E-Stop Show, and is used reset one of the Kp-300ʼs onboard latches to
allow the HPU to be started and the E-Stop conditions to be cleared.
Gilderfluke & Co.• 205 South Flower Street • Burbank, California 91502 • 818/840-9484 • 800/776-5972 • fax 818/840-9485
Kp-300 Manual / September 4, 2012 4:29 PM / page 59 of 75
17
This technique is flexible enough that you can even leave it out of any maintenance shows that you want to be able to run without
motion.