Kp-300
Operator Control Panel
The Kp-300 has all the controls that are needed to run any motion base or other
Smart Brick system. It mounts in 5-1/4” of standard 19” rack space. Operator controls
include buttons for starting and stopping the Hydraulic Power Unit (HPU), pausing and
then continuing a paused show, for ʻloggingʼ occupied seats, and for selecting and play-
ing up to eight different shows.
Because many of the functions of the Kp-300 are safety related, the Kp-300 has no
CPU of any kind. With no microcontroller, there is no possibility of a software crash.
Gilderfluke & Co.• 205 South Flower Street • Burbank, California 91502 • 818/840-9484 • 800/776-5972 • fax 818/840-9485
Kp-300 Manual / September 4, 2012 4:29 PM / page 1 of 75
Vue de la page 0
1 2 3 4 5 6 ... 74 75

Résumé du contenu

Page 1 - Operator Control Panel

Kp-300Operator Control PanelThe Kp-300 has all the controls that are needed to run any motion base or other Smart Brick system. It mou

Page 2

the Kp-300, remotely via a switch closure, or automatically as part of the motion profile program.Each safety input as well as the built in E-Stop

Page 3

Kp-300 Panel IndicatorsThere are sixty-one LED indicators and one or two LCD displays on the front of the Kp-300. They are used as follows:A) Error I

Page 4

All the inputs are configured to ʻfail safeʼ, which is to say that an error is triggered by an open circuit on an input. This is true even for the

Page 5 - This is not a blank page

the safety inputs can be logged by either pressing the Log Belts Button or activating the Remote Log Belts Input by pressing Remote Log Belts

Page 6 - A note about this manual:

The Show Cycle Count Advance Input pulse is typically programmed to take place towards the end of the motion base program. This lets a show

Page 7

from running. This technique should be used in applications that donʼt use the Blocking Valve Output. Typical of these are most electric moti

Page 8 - Valves, Cylinders

the HPUs wired into one of the error inputs of the Kp-300. This input is configured to keep the motion base from running if the HPU ʻHand/O

Page 9 - Kp-300 Overview

is started and a time after it is stopped where any HPU pressure sensors inputs will need to be bypassed. Do this by program-ming the Bypass

Page 10

vince the Kp-300 that the inputs are in the ʻsafeʼ position, and so they will not be logged as ʻunoccupiedʼ.The Show Pause functions are usually

Page 11 - Kp-300 Panel Indicators

disable the Kp-300 Show Pause functions. This is normally programmed ac-tive only during the E-Stop and Load/Unload shows.Seat belts can be logged

Page 12

Gilderfluke & Co.• 205 South Flower Street • Burbank, California 91502 • 818/840-9484 • 800/776-5972 • fax 818/840-9485Kp-300 Manual / September 4,

Page 13

Stopped Input. Unlike the HPU Running Input, this input is not used for any other purpose than lighting this LED.To help keep shows from being run w

Page 14

configured to pause the currently running show on a closure on this input5. When a show is 'continued', the signal is dropped on th

Page 15

Kp-300 Operator ControlsThe Kp-300 has just a small number of operator controls. Most of these have LEDs that can be lit under program control, or

Page 16

input together so it is always active. Whenever the Show Pause Reset Input is programmed active, the inputs that are set to be logged will automat

Page 17

If shows must be run in a certain order, you can program this into the mo-tion profile stored on the Smart Brick System. An example of this would be a

Page 18

E) HPU Stop ButtonThis Button is used to reset the latch on the Kp-300 that turns on the HPU Run Output. This is an optional feature. If you

Page 19

to pause the currently running show on a closure on this input8. When a show is 'continued', the signal is dropped on the Green ʻPauseʼ Ou

Page 20

Kp-300 Jumper ConfigurationThere are about seventy-five jumpers that must be set on the Kp-300 before it can be used. Not to worry though, each of the fi

Page 21

ommend that you document the final positions of all jumpers by marking them on the drawing above (or a copy of it) The jumpers are:A) Latched

Page 22 - Kp-300 Operator Controls

C) Seat Belt Logging(One jumper for each safety input)The fifteen Safety Inputs can be set to be ʻLoggedʼ either manually or automatically.

Page 23

...Kp-300 Overview! 9...

Page 24

By moving the jumper to the E-Stop position, an input will trigger an E-Stop show when it opens. Moving it to the Show Pause position will c

Page 25

ʻPauseʼ. Typically this is done during the E-Stop and Load/Unload shows to prevent these shows from being paused. F) Bypass Buss OneG) Bypass Buss Tw

Page 26

trigger an E-Stop, they will need to be bypassed during the E-Stop and Load Unload shows. This is because although you want these in

Page 27 - Kp-300 Jumper Configuration

Although any E-Stop error will stop the HPU, as soon as the E-Stop show has started running the HPU can be restarted. By using this jumper in addi-tio

Page 28 - External Power Internal Power

DipSwitch settings on the Kp-300 (v3.0+)(EIGHT POSITION DIPSWITCH)The DipSwitch is used to select several options on the v3.0+ Kp-300s:A) DipSwitch #1

Page 29 - E-Stop Show Pause

ON# = HPU-Stop Buss disables new show startsWhen on, this DipSwitch will keep any shows from being started When the HPU-Stop buss is active (th

Page 30

H) DipSwitch #8: Pause Buss Triggers Alarm OutputOFF# = Does nothingON# = Pause Buss Triggers Alarm OutputWhen on, when the Show Pause buss is active

Page 31 - Bypass #1 Bypass #2

DMX-512 Address Selection on the Kp-300 (v3.0+)(TWO HEXADECIMAL DIPSWITCHES)To support the DMX-512 input, the v3.0+ Kp-300 adds a two posi

Page 32

Sample ShowsAlthough the Kp-300 has no microcontroller on it of any kind, the Smart Brick System does. Whether or not the Smart Brick System is mo

Page 33

a) The motion base is programmed with all axis at the parked posi-tions. This can be seen in the upper, analog data pane. All the ana-log ch

Page 34 - IGHT POSITION DIPSWITCH)

...DipSwitch #5: Pause Buss Disables Show Starts! 35...DipSwitch

Page 35

j) Turn on/off any lights as needed to allow the passengers to be evacuated.k) On at least the first iteration of this show you will ne

Page 36

Moog E-Stop command requires that the PC under the Moog mo-tion base be rebooted before the motion base will move again. This is a little too dra

Page 37 - WO HEXADECIMAL DIPSWITCHES)

only the valid show selections. The eight ʻShow Pilotʼ outputs are shown doing a simple circular chase pattern.f) Whenever a Show Start Button

Page 38 - Sample Shows

they are automated they usually need to be programmed to open (or stay open) during the Load/Unload time.j) (optional) Turn on/off any lights as ne

Page 39

b) Enable the Blocking Valve Output to the Kp-300 just before mo-tion start. Disable it just after motion end. This will enable a hy-draulic Moti

Page 40

motion base is going to start moving, a hair before the Blocking Valve Output is programmed ON. This output is turned back ON as soon as the moti

Page 41

Program a Remote HPU Start Input into the show data. When the HPU is started as part of the motion profile, there will usually be a time just aft

Page 42

so that the ride is added to the running count.i) After the ʻCycle Counterʼ has been pulsed, and all the motion base axis have returned to t

Page 43

the list of shows that are to go into the AutoDownload. The order is unimportant, but we usually put the E-Stop and Load/Unload shows at the

Page 44

theses), or the settings on the last AutoDownload. Unless you have added or removed channels from your site file since the last Auto-Downl

Page 45

...Six High Current Optoisolated Outputs! 70...

Page 46

(assuming it is not getting realtime updates from Pc•MACs through the serial port or DMX-512), the Br-Brain4 will read in the AutoDownload file and

Page 47

cling on and off between every show is to use an extended load/unload show to turn off the HPU if the ride isnʼt restarted within a certain period of

Page 48

Power UpE-Stop 1ShowE-Stop 2ShowLoop until next show is startedLoad/UnloadLoop until next show is startedany E-Stop eventThe 'Show Start' bu

Page 49

Kp-300 ConnectionsThere are only four connectors on the Kp-300 (v1.n & v2.n) or seven connections (v3.0+) version Kp-300.Prior to the v

Page 50

tem. The v3.0+ Kp-300 has a separate pair of screw terminals for attaching the 24 vdc supply.Not surprisingly, the inputs to the Kp-300 are all com

Page 51

1. Show Start Button LED Inputs! Eight Inputs to Kp-300These inputs control the LEDs that are next to each of the eight Show Start Buttons.

Page 52

Typically the Show Start Buttons to call up all the shows that are loaded into Smart Brick System are programmed as active during the E-Stop

Page 53 - Kp-300 Connections

another. This makes it safe for you to configure the system to jump be-tween shows as described above.If you need show start switches that are externa

Page 54

motion base applications, the power is removed from the blocking valves during the Load/Unload times so that there is no possibility of the

Page 55

E-Stop and Load Unload shows. This is because although you want these inputs to trigger an error while the motion base is in moti

Page 56

Gilderfluke & Co.• 205 South Flower Street • Burbank, California 91502 • 818/840-9484 • 800/776-5972 • fax 818/840-9485Kp-300 Manual / September 4,

Page 57

4) Remote HPU Start Input to Kp-300This input is used by the motion control profile on the Smart Brick System to commands the HPU to start. T

Page 58

Input logging actually takes place at the instant that the Log Belts Button, Re-mote Log Belts Input, or Show Pause Reset Input are released.

Page 59

Kp-300 Outputs to Smart Brick Brain(20 POSITION RIBBON CABLE CONNECTOR)This connector is used to send messages and show requests from the Kp-300 to th

Page 60

1) Green ʻPauseʼ Output from Kp-300This output is activated when there is a Show Pause event on the Kp-300. This event causes the Pause Buss to go ac

Page 61 - WO POSITION SCREW TERMINAL)

J1 Inputs to the Kp-300(FEMALE DB-25 CONNECTOR)This connector is used for the first ten Error Inputs to the Kp-300. ! J1:!1 (-), 14 (+):!! Error Input

Page 62

J2 Inputs & Outputs to the Kp-300(MALE DB-25 CONNECTOR)This connector contains the remaining five Error Inputs, as well as the HPU Run

Page 63

This input should be fed 24 vdc from the HPU controller whenever the HPU is running. Unless this signal is received by the Kp-300, the Blocking Va

Page 64 - J1 Inputs to the Kp-300

error input which has been configured to force the HPU off. If the HPU is running, on the beginning of any E-Stop event, this output will be forced of

Page 65 - ALE DB-25 CONNECTOR)

sors, over temperature warnings, and other sensors on the HPU are often wired to these inputs.Each of these error inputs are optoisolated and c

Page 66

KP-300 Expansion • Gilderfluke & Company, Burbank, CaliforniaRelay Outputs1/4 J6 OutputsInputsJ6 Inputs3.0 3.1 3.2 3.3 3.4 3.5 3.6 3.72.0 2.1 2.2 2

Page 67

Gilderfluke & Co.• 205 South Flower Street • Burbank, California 91502 • 818/840-9484 • 800/776-5972 • fax 818/840-9485Kp-300 Manual / September 4,

Page 68

2) Six High Current Optoisolated Outputs(SIX 2 POSITION SCREW TERMINALS)These six optoisolated outputs can each sink one amp of current each, or a to

Page 69 - Kp-300 Expansion

The 24 vdc supply and ground lines can be used to power sensors or other de-vices. They are PTC fused for 1.1 amp of current.4) Thirty-two Optoisolate

Page 70 - WO FEMALE DB-25 CONNECTORS)

!35! Green! Bit 4! Error Input #29 To Kp-300 Expansion!36! Blue! Bit 3! Error Input #28 To Kp-300 Expansion!37! Violet! Bit 2! Error Input #27 To Kp-3

Page 71

Kp-300 Installation/Best PracticesThe Kp-300 is an operator panel, and with the addition of the Br-Brain4 and card cage on its back, it

Page 72

Gilderfluke & Co.• 205 South Flower Street • Burbank, California 91502 • 818/840-9484 • 800/776-5972 • fax 818/840-9485Kp-300 Manual / September 4,

Page 73

HEXadecimal to Decimal to PercentageThe following chart shows decimal, HEXadecimal, and a few percentage equivalents to aid you when you need to conve

Page 74

Gilderfluke & Co.• 205 South Flower Street • Burbank, California 91502 • 818/840-9484 • 800/776-5972 • fax 818/840-9485Kp-300 Manual / September 4,

Page 75

Kp-300 OverviewThe Kp-300 features fifteen safety inputs, plus an onboard E-Stop Button and Keyswitch that can be used to lock the system.